IDC (Internet Data Center) is a fast-growing industry along with the development of internet, it is not only a data storage center, but also a data exchange center, a key carrier of mass data, a core place of informatization. It is always a critical place with complexities, particularities and heavy investments, as well as fragility. There are many types of accidents in the IDC, fire/equip damage/communication-interruption, caused by direct lightning strikes/ induced surge/ overvoltage, might lead to the irreparable huge losses. In view of its characteristics, PTG provides a tailored lightning and surge protection solution.


According to the IDC protection requirement of IEC 62305, in order to determine the categories of LPZ (lightning protection zone) and SPD selection/installation, the below items must be taken into consideration:

     1. Lightning protection zone (LPZ 0…3);

     2. Relative SPD test waveshapes (8/20 μs or 10/350 μs);

     3. Voltage protection level

     4. Voltage and standard of power supply (230/400 V; 400/690 V; TT/TN system);

     5. Harmonic wave interference.

In accordance to:

     1. IEC 62305: Protection against Lightning

     2. IEC 61312: Protection against Lightning Electromagnetic Impulse

     3. IEC 61643-11: Low-voltage Surge Protective Devices

     4. IEC 61643-21: Surge protective devices connected to telecommunications and signaling networks - Performance requirements and testing methods


Related Products

  • Voltage transformer

    T1 PTE 320-25W1-30R used for 230/400 Vac TNC or IT power system to prevent direct lightning strike

    PTE 320-...W1-30R
  • Master power distribution cabinet

    T1 PTE 320-25W1-31R used for 230/400 Vac TT power system to prevent direct lightning strike

    PTE 320-...W1-31R
  • Power distribution box / RPP

    T2 PE 385-40M2-31R used for 230/400 Vac TT power system

    PE ...-...M2-31(R)
  • Terminal power distribution box

    T2 PE 385-40M2-11R used for 230/400 Vac single phase TT power system

    PE ...-40M2-11(R)
  • Diesel generator

    Type 1 SPD, PE 440-25W1-10R used for IT or TNC power system

    PE ... -25W1-10(R)
  • Internet communication system

    PD J5-2X1000-4 or PD J48-2X1000-4 used for cabling and PoE+ system

    PD J5-2X1000-4
    PD J48-2X1000-4
  • Control system

    PD LA-24W used for protecting signal system

    PD ...A-...WS
  • Lighting system

    Type 2 SPD, PE 275-40M2-11R used for 230/400 Vac single TT power system

    PE ...-40M2-11(R)
  • CCTV system

    2 in 1 integrated PE 385-10W2-21/J5-2X100-2 protects power/ veido/ control inferfaces

    PC ...-10W2-21/J5-2X100-2