BackModular SPD - Type 2
  • PTE 320-40M2-31(R)

PTE 320-40M2-31(R)

Part Name PTE 320-40M2-31R PTE 320-40M2-31
Approval KEMA, TUV, CE, UL
Technology MOV & GDT
Nominal Voltage (UN) 230 / 400 Vac
Max. continuous operating voltage (UC) 320 Vac (L-N), 255 Vac (N-PE)
Leakage current at voltage Uc ≤ 0.1 mA
Nominal discharge current (8/20 µs) (In) 20 kA
Max. discharge current (8/20 µs) (Imax) 40 kA
Voltage protection level (UP) 1.5 kV (L-N), 1.5kV (N-PE)
Voltage protection level for 5 kA (UP) 1.2 kV
Measured Limiting Voltage(MLV) 1330 V(L-N),1680 V(N-G)
Response time (tA) ≤ 25 ns
Max. overcurrent protection ≤ 125 AgL / gG
Short circuit withstand capability (ISCW) 25 kArms
Temporary overvoltage (TOV) (UT) 337 V / 5 s, 442V / 120min
TOV characteristic Withstand mode, Safety failure mode
Mechanical
Method of mounting 35 mm DIN rail
Enclosure dimensions (HxWxD) 90 mm × 72 mm × 66 mm
Cross-sectional area (max.) 25 mm² refer to flexible wire, 35 mm² refer to stranded wire
Cross-sectional area (min.) 1.5 mm² stranded / flexible
Stripping length terminals 10 mm
Torque contacts 3 N*m(Max), 2 N*m(Recommended)
Indication
Operating status/fault indication Green / red
Type of remote signaling contact Changeover contact ------
Switching capacity 125 Vac /1 A(Max), 5 V/0.5 mA(Min) ------
Cross-sectional area for remote signaling terminals(max.) 1.5 mm² -------
Stripping length for remote signaling terminals 7 mm ------
Torque contacts for indication terminals 0.2 N*m ------
Environmental
Location category Indoor only
Operation temperature range (TU) -40 °C ... +85 °C
Relative humidity ≤ 95 %(No condensation)
Operation altitude ≤ 4 km
Degree of protection IP 20
Enclosure material Thermoplastic, UL 94 V-0