Part Name
|
PTE 275-40M2-31R
|
PTE 275-40M2-31
|
Approval
|
KEMA, TUV, CE, UL
|
Technology
|
MOV & GDT
|
Nominal Voltage (UN)
|
230 / 400 Vac
|
Max. continuous operating voltage (UC)
|
275 Vac (L-N), 255 Vac (N-PE)
|
Leakage current at voltage Uc
|
≤ 0.1 mA
|
Nominal discharge current (8/20 µs) (In)
|
20 kA
|
Max. discharge current (8/20 µs) (Imax)
|
40 kA
|
Voltage protection level (UP)
|
1.3 kV (L-N), 1.5kV (N-PE)
|
Voltage protection level for 5 kA (UP)
|
1.0 kV
|
Measured Limiting Voltage(MLV)
|
1160 V(L-N),1680 V(N-G)
|
Response time (tA)
|
≤ 25 ns
|
Max. overcurrent protection
|
≤ 125 AgL / gG
|
Short circuit withstand capability (ISCW)
|
25 kArms
|
Temporary overvoltage (TOV) (UT)
|
337 V / 5 s, 442V / 120min
|
TOV characteristic
|
Withstand mode, Safety failure mode
|
Mechanical
|
Method of mounting
|
35 mm DIN rail
|
Enclosure dimensions (HxWxD)
|
90 mm × 72 mm × 66 mm
|
Cross-sectional area (max.)
|
25 mm² refer to flexible wire, 35 mm² refer to stranded wire
|
Cross-sectional area (min.)
|
1.5 mm² stranded / flexible
|
Stripping length terminals
|
10 mm
|
Torque contacts
|
3 N*m(Max), 2 N*m(Recommended)
|
Indication
|
Operating status/fault indication
|
Green / red
|
Type of remote signaling contact
|
Changeover contact
|
------
|
Switching capacity
|
125 Vac /1 A(Max), 5 V/0.5 mA(Min)
|
------
|
Cross-sectional area for remote signaling terminals(max.)
|
1.5 mm²
|
-------
|
Stripping length for remote signaling terminals
|
7 mm
|
------
|
Torque contacts for indication terminals
|
0.2 N*m
|
------
|
Environmental
|
Location category
|
Indoor only
|
Operation temperature range (TU)
|
-40 °C ... +85 °C
|
Relative humidity
|
≤ 95 %(No condensation)
|
Operation altitude
|
≤ 4 km
|
Degree of protection
|
IP 20
|
Enclosure material
|
Thermoplastic, UL 94 V-0
|